Skip to main content

Understanding NEC 240.15: Overcurrent Protection for Ungrounded Conductors

240.15 Ungrounded Conductors

240.15 Ungrounded Conductors

(A) Overcurrent Device Required

A fuse or an overcurrent trip unit of a circuit breaker shall be connected in series with each ungrounded conductor. A combination of a current transformer and overcurrent relay shall be considered equivalent to an overcurrent trip unit.

Note: For motor circuits, see Parts III, IV, V, and XI of Article 430.

(B) Circuit Breaker as Overcurrent Device

Circuit breakers shall open all ungrounded conductors of the circuit both manually and automatically unless otherwise permitted in 240.15(B)(1), (B)(2), and (B)(3).

(1) Multiwire Branch Circuit

Except where limited by 210.4(B), individual single-pole circuit breakers, with or without identified handle ties, shall be permitted as the protection for each ungrounded conductor of multiwire branch circuits that serve only single-phase line-to-neutral loads.

(2) Grounded Single-Phase and 3-Wire DC Circuits

In grounded systems, individual single-pole circuit breakers with identified handle ties shall be permitted as the protection for each ungrounded conductor for line-to-line connected loads for single-phase circuits or 3-wire, direct-current circuits.

(3) 3-Phase and 2-Phase Systems

For line-to-line loads in 4-wire, 3-phase systems or 5-wire, 2-phase systems having a grounded neutral point and no conductor operating at a voltage greater than permitted in 210.6, individual single-pole circuit breakers with identified handle ties shall be permitted as the protection for each ungrounded conductor.

(C) Closed-Loop Power Distribution Systems

Listed devices that provide equivalent overcurrent protection in closed-loop power distribution systems shall be permitted as a substitute for fuses or circuit breakers.

Understanding NEC 240.15: Overcurrent Protection for Ungrounded Conductors

Comments

Popular posts from this blog

Understanding NEC 700.10: Wiring Requirements for Emergency Systems

Comprehensive Guide to NEC 700.10: Wiring Emergency Systems Comprehensive Guide to NEC 700.10: Wiring Emergency Systems The National Electrical Code (NEC) Section 700.10 provides critical guidelines for the wiring of emergency systems. These systems ensure continued operation during power outages, protecting lives and maintaining functionality in key buildings. This guide breaks down the essential requirements of Section 700.10 to help ensure compliance and reliability. 1. Identification of Emergency Circuits Proper identification is essential for emergency systems to avoid confusion during maintenance or emergencies. The NEC mandates: Permanent Marking: All boxes, enclosures, transfer switches, generators, and power panels used for emergency circuits must be clearly marked. Cable and Raceway Systems: If boxes or enclosures are absent, exposed cables or raceways must be marked at intervals not exceeding 25 feet. ...

NEC 310.4 Compliance: Rules for Parallel Conductors

310.4 Conductors in Parallel 310.4 Conductors in Parallel (A) General Aluminum, copper-clad aluminum, or copper conductors of size 1/0 AWG and larger can be connected in parallel for each phase, polarity, neutral, or grounded circuit conductor. Exception No. 1 Conductors smaller than 1/0 AWG are allowed for specific applications, such as control power for instruments, contactors, relays, etc., or for frequencies of 360 Hz and higher , provided: They are in the same raceway or cable. Each conductor can carry the entire load current. Overcurrent protection ensures no conductor exceeds its ampacity if one or more parallel conductors are disconnected. Exception No. 2 Under engineering supervision, grounded neutral conductors of 2 AWG and larger can be run in parallel for existing i...

NEC Rules for Service Conductors and Fire Pump Feeders

NEC Code: Service Conductors & Fire Pump Feeder Requirements NEC Code: Service Conductors & Fire Pump Feeder Requirements The National Electrical Code (NEC) outlines specific guidelines for the installation and routing of service conductors and fire pump feeder conductors to ensure safety and compliance. Here’s what you need to know: 230.6: Service Conductors and On-Site Power Production Facilities Service conductors and conductors powered by on-site facilities must be: Routed Outside the Building: They should primarily be installed outside the building(s). Exception: If external routing isn’t possible, they may be routed through the building, following specific NEC standards in 230.6(1) or (2) . Fire Pump Feeder Conductors (695.6) Fire pump systems have stringent requirements to ensure functionality during emergencies: (a) Independent Routing: Conductors must be...