Skip to main content

Understanding NEC 240.15: Overcurrent Protection for Ungrounded Conductors

240.15 Ungrounded Conductors

240.15 Ungrounded Conductors

(A) Overcurrent Device Required

A fuse or an overcurrent trip unit of a circuit breaker shall be connected in series with each ungrounded conductor. A combination of a current transformer and overcurrent relay shall be considered equivalent to an overcurrent trip unit.

Note: For motor circuits, see Parts III, IV, V, and XI of Article 430.

(B) Circuit Breaker as Overcurrent Device

Circuit breakers shall open all ungrounded conductors of the circuit both manually and automatically unless otherwise permitted in 240.15(B)(1), (B)(2), and (B)(3).

(1) Multiwire Branch Circuit

Except where limited by 210.4(B), individual single-pole circuit breakers, with or without identified handle ties, shall be permitted as the protection for each ungrounded conductor of multiwire branch circuits that serve only single-phase line-to-neutral loads.

(2) Grounded Single-Phase and 3-Wire DC Circuits

In grounded systems, individual single-pole circuit breakers with identified handle ties shall be permitted as the protection for each ungrounded conductor for line-to-line connected loads for single-phase circuits or 3-wire, direct-current circuits.

(3) 3-Phase and 2-Phase Systems

For line-to-line loads in 4-wire, 3-phase systems or 5-wire, 2-phase systems having a grounded neutral point and no conductor operating at a voltage greater than permitted in 210.6, individual single-pole circuit breakers with identified handle ties shall be permitted as the protection for each ungrounded conductor.

(C) Closed-Loop Power Distribution Systems

Listed devices that provide equivalent overcurrent protection in closed-loop power distribution systems shall be permitted as a substitute for fuses or circuit breakers.

Understanding NEC 240.15: Overcurrent Protection for Ungrounded Conductors

Comments

Popular posts from this blog

Cable Sizing and Overload Protection for Motors

Abstract of National Electrical Code for Size of Cable for Motors Abstract of National Electrical Code for Size of Cable for Motors National Electrical Code 430.22 (Size of Cable for Single Motor) The size of the cable for a branch circuit that has a single motor connection must be 125% of the motor's full load current capacity. Example: What is the minimum rating in amperes for cables supplying one number of 5 horsepower, 415-volt, 3-phase motor at 0.8 power factor? Full-load current for 5 horsepower = 7 amperes. Minimum capacity of cable = (7 × 125%) = 8.75 amperes. National Electrical Code 430.6(A) (Size of Cable for Group of Motors or Electrical Load) Cables or feeders supplying more than one motor or other loads must have an ampacity not less than 125% of the full-load current rating of the highest rated motor plus the sum of the full-load current ratings of all the other motors in the group, as det...

Understanding NEC 700.10: Wiring Requirements for Emergency Systems

Comprehensive Guide to NEC 700.10: Wiring Emergency Systems Comprehensive Guide to NEC 700.10: Wiring Emergency Systems The National Electrical Code (NEC) Section 700.10 provides critical guidelines for the wiring of emergency systems. These systems ensure continued operation during power outages, protecting lives and maintaining functionality in key buildings. This guide breaks down the essential requirements of Section 700.10 to help ensure compliance and reliability. 1. Identification of Emergency Circuits Proper identification is essential for emergency systems to avoid confusion during maintenance or emergencies. The NEC mandates: Permanent Marking: All boxes, enclosures, transfer switches, generators, and power panels used for emergency circuits must be clearly marked. Cable and Raceway Systems: If boxes or enclosures are absent, exposed cables or raceways must be marked at intervals not exceeding 25 feet. ...