Skip to main content

Understanding NEC 250.118: Approved Equipment Grounding Conductors

NEC 250.118: Types of Equipment Grounding Conductors

NEC 250.118: Types of Equipment Grounding Conductors

Overview

The equipment grounding conductor installed alongside or enclosing the circuit conductors must adhere to specific types as outlined in the NEC. These ensure the safety and effectiveness of the grounding system.

Note: Refer to 250.2 for the definition of an effective ground-fault current path.

Types of Equipment Grounding Conductors

  • (1) Metal Conductors

    Includes copper, aluminum, or copper-clad aluminum conductors, which can be solid or stranded, insulated, covered, or bare, and shaped as a wire or busbar.

  • (2) Rigid Metal Conduit (RMC)

    Provides a durable and effective grounding path.

  • (3) Intermediate Metal Conduit (IMC)

    A suitable metal pathway for grounding conductors.

  • (4) Electrical Metallic Tubing (EMT)

    Offers grounding and physical protection for circuit conductors.

  • (5) Listed Flexible Metal Conduit (FMC)

    Permitted when:

    • Terminated in listed fittings.
    • Overcurrent devices rated at ≤ 20 amperes protect the circuit conductors.
    • Total length of all flexible conduits in the ground path does not exceed 1.8 m (6 ft).
    • An additional equipment grounding conductor is installed for flexible connections.
  • (6) Listed Liquidtight Flexible Metal Conduit (LFMC)

    Allowed under these conditions:

    • Terminated in listed fittings.
    • For trade sizes 3⁄8 to 1⁄2, conductors protected by ≤ 20-ampere devices.
    • For trade sizes 3⁄4 to 1-1⁄4, conductors protected by ≤ 60-ampere devices.
    • Total flexible conduit length in the grounding path ≤ 1.8 m (6 ft).
    • Additional equipment grounding conductor is required for flexible installations.
  • (7) Flexible Metallic Tubing (FMT)

    Permitted when:

    • Circuit conductors protected by ≤ 20-ampere devices.
    • Grounding path length ≤ 1.8 m (6 ft).
  • (8) Armor of Type AC Cable

    Grounding permitted as outlined in 320.108.

  • (9) Copper Sheath of Mineral-Insulated Cable (Type MI)

    Provides effective grounding.

  • (10) Type MC Cable

    Must be listed and identified for grounding:

    • Includes interlocked metal tape or corrugated metallic sheaths.
  • (11) Cable Trays

    Permitted as per 392.3 and 392.7.

  • (12) Cablebus Framework

    Allowed under 370.3.

  • (13) Listed Electrically Continuous Metal Raceways

    Includes raceways and listed auxiliary gutters.

  • (14) Listed Surface Metal Raceways

    Specifically listed for grounding purposes.

Comments

Popular posts from this blog

Cable Sizing and Overload Protection for Motors

Abstract of National Electrical Code for Size of Cable for Motors Abstract of National Electrical Code for Size of Cable for Motors National Electrical Code 430.22 (Size of Cable for Single Motor) The size of the cable for a branch circuit that has a single motor connection must be 125% of the motor's full load current capacity. Example: What is the minimum rating in amperes for cables supplying one number of 5 horsepower, 415-volt, 3-phase motor at 0.8 power factor? Full-load current for 5 horsepower = 7 amperes. Minimum capacity of cable = (7 × 125%) = 8.75 amperes. National Electrical Code 430.6(A) (Size of Cable for Group of Motors or Electrical Load) Cables or feeders supplying more than one motor or other loads must have an ampacity not less than 125% of the full-load current rating of the highest rated motor plus the sum of the full-load current ratings of all the other motors in the group, as det...

Understanding NEC 240.15: Overcurrent Protection for Ungrounded Conductors

240.15 Ungrounded Conductors 240.15 Ungrounded Conductors (A) Overcurrent Device Required A fuse or an overcurrent trip unit of a circuit breaker shall be connected in series with each ungrounded conductor. A combination of a current transformer and overcurrent relay shall be considered equivalent to an overcurrent trip unit. Note: For motor circuits, see Parts III, IV, V, and XI of Article 430. (B) Circuit Breaker as Overcurrent Device Circuit breakers shall open all ungrounded conductors of the circuit both manually and automatically unless otherwise permitted in 240.15(B)(1), (B)(2), and (B)(3). (1) Multiwire Branch Circuit Except where limited by 210.4(B), individual single-pole circuit breakers, with or without identified handle ties, shall be permitted as the protection for each ungrounded conductor of multiwire branch circuits that serve only single-phase line-to-neutral loads. (2)...

Understanding NEC 700.10: Wiring Requirements for Emergency Systems

Comprehensive Guide to NEC 700.10: Wiring Emergency Systems Comprehensive Guide to NEC 700.10: Wiring Emergency Systems The National Electrical Code (NEC) Section 700.10 provides critical guidelines for the wiring of emergency systems. These systems ensure continued operation during power outages, protecting lives and maintaining functionality in key buildings. This guide breaks down the essential requirements of Section 700.10 to help ensure compliance and reliability. 1. Identification of Emergency Circuits Proper identification is essential for emergency systems to avoid confusion during maintenance or emergencies. The NEC mandates: Permanent Marking: All boxes, enclosures, transfer switches, generators, and power panels used for emergency circuits must be clearly marked. Cable and Raceway Systems: If boxes or enclosures are absent, exposed cables or raceways must be marked at intervals not exceeding 25 feet. ...