Skip to main content

Understanding NEC 250.118: Approved Equipment Grounding Conductors

NEC 250.118: Types of Equipment Grounding Conductors

NEC 250.118: Types of Equipment Grounding Conductors

Overview

The equipment grounding conductor installed alongside or enclosing the circuit conductors must adhere to specific types as outlined in the NEC. These ensure the safety and effectiveness of the grounding system.

Note: Refer to 250.2 for the definition of an effective ground-fault current path.

Types of Equipment Grounding Conductors

  • (1) Metal Conductors

    Includes copper, aluminum, or copper-clad aluminum conductors, which can be solid or stranded, insulated, covered, or bare, and shaped as a wire or busbar.

  • (2) Rigid Metal Conduit (RMC)

    Provides a durable and effective grounding path.

  • (3) Intermediate Metal Conduit (IMC)

    A suitable metal pathway for grounding conductors.

  • (4) Electrical Metallic Tubing (EMT)

    Offers grounding and physical protection for circuit conductors.

  • (5) Listed Flexible Metal Conduit (FMC)

    Permitted when:

    • Terminated in listed fittings.
    • Overcurrent devices rated at ≤ 20 amperes protect the circuit conductors.
    • Total length of all flexible conduits in the ground path does not exceed 1.8 m (6 ft).
    • An additional equipment grounding conductor is installed for flexible connections.
  • (6) Listed Liquidtight Flexible Metal Conduit (LFMC)

    Allowed under these conditions:

    • Terminated in listed fittings.
    • For trade sizes 3⁄8 to 1⁄2, conductors protected by ≤ 20-ampere devices.
    • For trade sizes 3⁄4 to 1-1⁄4, conductors protected by ≤ 60-ampere devices.
    • Total flexible conduit length in the grounding path ≤ 1.8 m (6 ft).
    • Additional equipment grounding conductor is required for flexible installations.
  • (7) Flexible Metallic Tubing (FMT)

    Permitted when:

    • Circuit conductors protected by ≤ 20-ampere devices.
    • Grounding path length ≤ 1.8 m (6 ft).
  • (8) Armor of Type AC Cable

    Grounding permitted as outlined in 320.108.

  • (9) Copper Sheath of Mineral-Insulated Cable (Type MI)

    Provides effective grounding.

  • (10) Type MC Cable

    Must be listed and identified for grounding:

    • Includes interlocked metal tape or corrugated metallic sheaths.
  • (11) Cable Trays

    Permitted as per 392.3 and 392.7.

  • (12) Cablebus Framework

    Allowed under 370.3.

  • (13) Listed Electrically Continuous Metal Raceways

    Includes raceways and listed auxiliary gutters.

  • (14) Listed Surface Metal Raceways

    Specifically listed for grounding purposes.

Comments

Popular posts from this blog

Understanding NEC 700.10: Wiring Requirements for Emergency Systems

Comprehensive Guide to NEC 700.10: Wiring Emergency Systems Comprehensive Guide to NEC 700.10: Wiring Emergency Systems The National Electrical Code (NEC) Section 700.10 provides critical guidelines for the wiring of emergency systems. These systems ensure continued operation during power outages, protecting lives and maintaining functionality in key buildings. This guide breaks down the essential requirements of Section 700.10 to help ensure compliance and reliability. 1. Identification of Emergency Circuits Proper identification is essential for emergency systems to avoid confusion during maintenance or emergencies. The NEC mandates: Permanent Marking: All boxes, enclosures, transfer switches, generators, and power panels used for emergency circuits must be clearly marked. Cable and Raceway Systems: If boxes or enclosures are absent, exposed cables or raceways must be marked at intervals not exceeding 25 feet. ...

NEC 310.4 Compliance: Rules for Parallel Conductors

310.4 Conductors in Parallel 310.4 Conductors in Parallel (A) General Aluminum, copper-clad aluminum, or copper conductors of size 1/0 AWG and larger can be connected in parallel for each phase, polarity, neutral, or grounded circuit conductor. Exception No. 1 Conductors smaller than 1/0 AWG are allowed for specific applications, such as control power for instruments, contactors, relays, etc., or for frequencies of 360 Hz and higher , provided: They are in the same raceway or cable. Each conductor can carry the entire load current. Overcurrent protection ensures no conductor exceeds its ampacity if one or more parallel conductors are disconnected. Exception No. 2 Under engineering supervision, grounded neutral conductors of 2 AWG and larger can be run in parallel for existing i...

NEC Rules for Service Conductors and Fire Pump Feeders

NEC Code: Service Conductors & Fire Pump Feeder Requirements NEC Code: Service Conductors & Fire Pump Feeder Requirements The National Electrical Code (NEC) outlines specific guidelines for the installation and routing of service conductors and fire pump feeder conductors to ensure safety and compliance. Here’s what you need to know: 230.6: Service Conductors and On-Site Power Production Facilities Service conductors and conductors powered by on-site facilities must be: Routed Outside the Building: They should primarily be installed outside the building(s). Exception: If external routing isn’t possible, they may be routed through the building, following specific NEC standards in 230.6(1) or (2) . Fire Pump Feeder Conductors (695.6) Fire pump systems have stringent requirements to ensure functionality during emergencies: (a) Independent Routing: Conductors must be...